TMP for gas turbines F8-H10
|
Technical information (PDF 864 kB) The TMP compact filter elements consist of 4 V elements on both sides sealed with polyurethane in a plastic frame. The two-sided sealing of the filter pleat makes the filter resistant to dripping condensate and ensures a long useful life under extreme conditions. Field of application: Gas turbines, plate power units, compressors, and air conditioning units of power plants. Waste disposal: Incineration in authorised incineration plants. |
| Technická data dle EN 779 a EN 1822 | KS TMP | KS TMPC | |
| Filtration class | F8 | F9 | E10 |
| Material | Glass submicron filter paper | ||
| Possibility of regeneration | No | ||
| Supply of material | 592 x 592, 287 x 592, 490 x 592, 402 x 592 | ||
| Mean efficiency degree (gravimetric) (%) | 99 | ∼ 100 | ∼ 100 |
| Mean efficiency degree (atmospheric) (%) | 93 | 96 | 98 |
| Nominal air flow rate (m3/h) VR/VN | 3400/4250 | 3400/42503000/3400 | |
| Initial pressure loss at nominal load (Pa) VR/VN | 90/125 | 95/135120/140 | |
| Recommended final pressure loss (Pa) | 450 | 450450 | |
| Maximum thermal resistance (max °C) | ≤70 | ≤70 | |
Pressure loss diagram