TMP for gas turbines F6-F7
|
Technical information (PDF 864 kB) The TMP compact filter elements consist of 4 V elements on both sides sealed with polyurethane in a plastic frame. The two-sided sealing of the filter pleat makes the filter resistant to dripping condensate and ensures a long useful life under extreme conditions. Field of application: Gas turbines, plate power units, compressors, and air conditioning units of power plants. Waste disposal: Incineration in authorised incineration plants. |
| Technická data dle EN 779 | KS TMP | |
| Filtration class | F6 | F7 |
| Material | Glass submicron filter paper | |
| Possibility of regeneration | No | |
| Supply of material | 592 x 592, 287 x 592, 490 x 592, 402 x 592 | |
| Mean efficiency degree (gravimetric) (%) | 98 | 99 |
| Mean efficiency degree (atmospheric) (%) | 70 | 86 |
| Nominal air flow rate (m3/h) VR/VN | 3400/4200 | 3400/4250 |
| Initial pressure loss at nominal load (Pa) | 65/95 | 70/105 |
| Recommended final pressure loss (Pa) | 450 | 450 |
| Maximum thermal resistance (max °C) | ≤70 | |
Pressure loss diagram