Compact filter elements KS FP M6 - F9

Compact filter elements KS FP M6 - F9 Technical information (PDF 68,2 kB)

The compact filter elements provide an up-to-date and effective solution for separating fine dust. The glass fibre medium (special filter paper) forms V-shaped pleats and is inserted into a plastic frame. The filters have an excellent price/performance ratio.

Field of application: They are used as after-filters or microparticles pre-filters in air conditioning and ventilation units of all types.
Waste disposal: Incineration without emission of harmful pollutants.
NT = standard temperature; HT special design for high temperatures - not available for KS FP M6

Technical data according to EN 1822KS FP
Filtration classM6F7F8F9
MaterialGlass submicron filter paper
Possibility of regenerationNo
Supply of material 592 x 592, 287 x 592, 490 x 592, 402 x 592
Mean efficiency degree (gravimetric) (%)989999∼ 100
Mean efficiency degree (atmospheric) (%)60-8080-9090-95>95
Nominal air flow rate (m3/h)3400340034003400
Initial pressure loss at nominal load (Pa)75809098
Recommended final pressure loss (Pa)450450450450
Maximum thermal resistance (max °C)NT = 75; HT = 120

Pressure loss diagram
Pressure loss diagram