Compact filter elements KS FP F6 - F9
|
Technical information (PDF 700 kB) The compact filter elements provide an up-to-date and effective solution for separating fine dust. The glass fibre medium (special filter paper) forms V-shaped pleats and is inserted into a plastic frame. The filters have an excellent price/performance ratio. Field of application: They are used as after-filters or microparticles pre-filters in air conditioning and ventilation units of all types. Waste disposal: Incineration without emission of harmful pollutants. NT = standard temperature; HT special design for high temperatures - not available for KS FP F6 |
| Technical data according to EN 1822 | KS FP | |||
| Filtration class | F6 | F7 | F8 | F9 |
| Material | Glass submicron filter paper | |||
| Possibility of regeneration | No | |||
| Supply of material | 592 x 592, 287 x 592, 490 x 592, 402 x 592 | |||
| Mean efficiency degree (gravimetric) (%) | 98 | 99 | 99 | ∼ 100 |
| Mean efficiency degree (atmospheric) (%) | 70 | 82 | 93 | 96 |
| Nominal air flow rate (m3/h) | 4250 | 4250 | 4250 | 3400 |
| Initial pressure loss at nominal load (Pa) | 105 | 105 | 120 | 105 |
| Recommended final pressure loss (Pa) | 450 | 450 | 450 | 450 |
| Maximum thermal resistance (max °C) | NT = 75; HT = 120 | |||
Pressure loss diagram